Soft PLC Signals
parameter ID | Name | Direction | Description |
---|---|---|---|
10010 | Start tightening (continuous) | Input | Active signal starts tightening. Once input goes inactive the tightening must be stopped. |
10016 | Select input bit 0 | Input | Input signal for select bit 0. |
10017 | Select input bit 1 | Input | Input signal for select bit 1. |
10018 | Select input bit 2 | Input | Input signal for select bit 2. |
10019 | Select input bit 3 | Input | Input signal for select bit 3. |
10020 | Select input | Input | Input selected value. |
10024 | Tightening + start (pulse) | Input | The tightening starts at signal. Runs until the tightening is finished, or until the 30 sec timeout in tightening program occurs. |
10030 | Tightening/Loosening stop (pulse) | Input | If this signal is generated any ongoing tightening or loosening will be stopped. Used in combination with 10024. |
10045 | External Identifier | Input/Output | Provide up to 2 identifiers to be passed from Fieldbus for task selection. |
10049 | Disable Fieldbus | Input | Disables the fieldbus. |
10066 | Select input bit 4 | Input | Input signal for select bit 4 |
10067 | Select input bit 5 | Input | Input signal for select bit 5 |
10068 | Select input bit 6 | Input | Input signal for select bit 6 |
10069 | Select input bit 7 | Input | Input signal for select bit 7 |
10070 | Select input bit 8 | Input | Input signal for select bit 8 |
10071 | Select input bit 9 | Input | Input signal for select bit 9 |
10072 | Loosening start (pulse) | Input | Loosening sync mode is started when this signal goes high. ![]() Runs until the loosening is finished, even if the Loosening Start (pulse) signal goes low. |
10064 | From PLC | Input | Byte array that carries information from the SoftPLC to the Accessories. |
10054 | Channel Command | Input | With the channel command it is possible to inhibit individual tools so they are not included in the next tightening. |
10055 | Enable Operation | Input | Must be set high to be able to run a tightening in a fixtured system. It is set to low during a tightening, the tightening is stopped and the status of the cycle is NOK. |
10056 | Reset Cycle Status | Input | When Reset Cycle Status is set to true, reset of the status of the station and all bolts will be performed. ![]() If this signal is set during a tightening, the signal is ignored. |
10057 | Disable Testbolt | Input | The signal controls if the test bolt can be performed or not from external source. If the signal is True (high), it is not possible to perform test bolt from an external source. |
10062 | Reset System Error | Input | If this input is set to high, the system will try to reset any hardware errors. |
82 | Cycle Ready to Start | Output | The signal is set high when the system is ready to start a tightening. The system is ready if the following conditions are fulfilled:
|
78 | Cycle Running | Output | Set high while the system is running a tightening. |
77 | Cycle Complete | Output | Set high when the running cycle is completed and the data is stored persistently. |
75 | Cycle OK | Output | Set high if the last tightening was OK and is cleared when the start signal is received. |
76 | Cycle NOK | Output | Set high if the last tightening was NOK and is cleared when the start signal is received. |
83 | No System Error | Output | The No System Error is set to true if there are no hardware errors in the system. |
91 | Testbolt Activated | Output | Testbolt Activated is used to display if test tightening is enabled. |
20036 | Emergency Stop | Output | Set high if the system is emergency stopped. |
42 | IO ON | Output | Controller switched On. |
96 | Fiedbus Disconnected | Output | Fieldbus Disconnected will be set to True when fieldbus disconnects. |
102 | No System Warning | Output | No System Warning is set High if any of the tools report “time for service” or “time for calibration”. |
100 | Identifier Received | Output | Identifier received is used to indicate that a new identifier has been received. |
72 | Selected Mode ID | Output | Selected Mode ID mirrors the Input Mode Value if the mode is valid. If the mode is invalid or no mode is selected, "0" will be sent. |
79 | Bolt Tightening Status | Output | Status for individual bolts in a synchronized tightening. 100 bolts are supported. |
80 | Channel Tightening Status | Output | Status for individual channels in a synchronized tightening. 64 channels are supported. |
81 | Channel Hardware Status | Output | Hardware status for individual channels. |
85 | Software Release Version | Output | Release version of the software running in the controller. |
86 | Software Major Version | Output | Major version of the software running in the controller. |
87 | Software Minor Version | Output | Minor version of the software running in the controller. |
88 | Configuration Version | Output | Version of the configuration currently used in the controller. |
10065 | To PLC | Output | Byte array that carries information from the accessories to the SoftPLC. |