Internal I/O Module

Inputs/outputs:

8 digital inputs and outputs (24VDC)

Communication protocol:

Modbus

Expandable by adding:

Up to 7 extension modules each with 8 inputs and outputs;
extension modules need their own 24VDC supply

Current per output (internally limited by PTC):

0,2A (500mA over all 8 outputs at a time loadable)

Current consumption per input:

7mA

  • Outputs are protected against short circuits, overload, load dump (inductive voltage spikes) as well as the loss of ground connection.

  • Reversing the polarity of the supply voltage will destroy the internal soldered fuse.