Event codes

Error code

Event information

Instruction

101

Supply voltage exceeded

Check power supply.

102

Supply voltage too low

Check power supply.

103

Internal 24V exceeded

Disconnect external equipment.

104

Internal 24V too low

Disconnect external equipment.

105

Internal 12V exceeded

Disconnect tool if connected.

106

Internal 12V too low

Disconnect tool if connected.

107

Internal 5V exceeded

Disconnect tool if connected.

108

Internal 5V too low

Disconnect tool if connected.

109

External 24V error

Disconnect external equipment, restart controller.

110

DC/DC temperature error

Replace the controller.

111

I/O expanders reinitialized

Press OK to continue.

112

Failed to reinitialize I/O

Restart the controller.

113

Power fault

Check power supply.

120

Zero offset error, Current

Replace the controller.

121

Zero offset error, Sensor

Replace the tool transducer or the tool.

122

Motor current low

Replace the tool.

123

Motor current exceeded

Replace the tool.

124

Motor driver voltage too low

Replace the tool.

125

Motor driver short circuit

Replace the tool.

126

Motor driver temperature exceeded

Replace the tool.

127

Motor driver open load

Replace the tool.

128

Motor driver fault

Restart the controller.

130

EEPROM read error

Replace the controller.

131

EEPROM write error

Replace the controller.

132

Internal hardware error

Replace the controller.

133

File system error

Replace IAM MT.

134

USB host overcurrent

Disconnect USB devices.

135

USB flash drive volume error

Try another USB flash drive.

140

No tool connected

Connect tool.

141

Tool not supported

Connect supported tool.

142

Tool communication error

Replace the tool.

143

Tool 5V error

Replace the tool.

144

Tool 12V error

Replace the tool.

150

Tool initializing error

Check that the tool is running freely during start up.

151

Friction too high

Check that the tool is running freely during start up.

152

Tool angle encoder error

Connect tool.

153

Tool direction error

Connect tool.

154

Bit was blocked

Check that the tool is running freely during start up.

155

Tool motor temperature exceeded

Allow time for tool to cool down.

156

Tool not supported

Transducerized tools not supported by current license.

157

Failed to update tool software

Disconnect transducer.

158

Tool initialization error

159

Torque measurement warning

Calibrate the tool.

160

Torque measurement error

Calibrate the tool.

201

Runtime parameter error

Restart the controller.

202

Invalid controller parameters

Replace IAM MT.

203

Invalid controller parameters

Replace the tool

204

Invalid I/O parameters

Replace IAM MT.

205

Invalid identifier parameters

Replace IAM MT.

206

Invalid Pset parameters

Replace IAM MT.

207

Invalid Batch sequence parameters

Replace IAM MT.

208

Invalid password parameters

Replace IAM MT.

209

Tool statistics error.

Replace the tool.

210

Unable to load fonts from IAM MT

Replace IAM MT.

211

Invalid tool configuration parameters

Replace IAM MT.

212

Invalid operator parameters

Replace IAM MT.

220

Result database error

Replace IAM MT.

221

Graph database error

Replace IAM MT.

225

Reset result database

Result database was reset.

226

Reset graph database

Graph database was reset.

227

No results to export - database empty

228

Old results removed

229

Old graphs removed

230

Pset not configured for connected tool

Select another Pset or configure new Pset in ToolsTalk MT.

231

Select error source

Change select source. Can be changed in ToolsTalk MT Controller settings.

232

Select error busy

Wait until tool is not running.

240

Network configuration has an error

Change network configuration.

241

IP address and gateway not in same subnet

Change network configuration.

301

Tool connected

Press OK to initialize the tool.

302

Tool initializing

Please wait.

303

Tool software updating

Please wait.

304

Tool software update error

Check tool cable or replace the tool.

305

Tool calibration required

Calibrate the tool.

306

Service required

Tool calibration has expired. Calibrate the tool.

310

Software has been updated

Press OK to continue.

311

Software file wasn't found on USB

Copy software file to USB flash drive.

312

Software update failed

Software file on USB may be broken. Update software file on USB and try again.

313

Copying software

Please wait. Software is being copied to/from USB.

314

Can only show first 20 .mtp or .fw files

Press OK to continue.

315

Software update failed - incompatible hardware

320

Login expired

User was logged out.

321

User has logged in

322

The current user has logged out

350

Battery adapter hardware error

351

Battery adapter temperature exceeded

Let battery to cool down.

352

Battery adapter charge fault

Change battery.

353

Battery temperature error

Let battery to cool down.

354

Battery discharge error

Connect PSU to charge battery.

355

Battery charge critically low

Connect PSU to charge battery.

356

Battery not supported

Change battery.

357

Battery adapter charge fault

Change battery.

358

Battery adapter charge fault

Let battery cool down or change battery.

401

Tightening error

Press OK to continue

402

Batch sequence error

Press OK to continue

403

Batch sequence parameter error

Check controller to see which parameter is incorrect

404

Pset not supported

Select another Pset

405

Pset parameter error

Update Pset.

507

ToolsNet skipped result

601

Controller communication error

602

Transducer communication error

603

Measurement data lost due to lost USB link

604

Transducer connected

605

No transducer detected

Connect transducer and try again.

606

Remote device is busy

Try again later.

607

Transducer service required

608

Zero offset error, Transducer

Check that the transducer cable is fastened correctly or replace cable/transducer.

609

Operator ID required by active verification

Scan operator ID.

610

Connected device is not compatible with QA

701

Fieldbus not supported by controller HW

Replace controller with rev C or higher.

702

Invalid fieldbus parameters

Replace IAM MT.

703

Fieldbus module error

Check fieldbus cable or replace the fieldbus module, press OK to continue.

704

Fieldbus driver warning

Check for firmware update, press OK to continue.

705

Fieldbus driver error

Check for firmware update.

706

Fieldbus module in error state

Check fieldbus network status.

707

Fieldbus module in exception state

Check for firmware update.

720

Fieldbus module not connected

Connect fieldbus module, check fieldbus cable or replace the fieldbus module.

721

Fieldbus module not supported, wrong module type

Connect supported fieldbus module.

722

Fieldbus module not supported, wrong network type

Connect supported fieldbus module.

723

Fieldbus module not supported, wrong provider ID

Connect supported fieldbus module.

724

Fieldbus module not supported, FW version not approved

Connect supported fieldbus module.

730

Fieldbus not configured for connected module

Change configuration of fieldbus type or connect correct module.

731

Fieldbus parameter error

Update fieldbus parameters and press OK.

732

Fieldbus configuration of network settings failed

Check that fieldbus setup is ok and try again.

740

Max 128 submodules supported for Profinet

Update fieldbus parameters and press OK.

741

Profinet station name syntax error

Update fieldbus parameters and press OK.

901

IAM MT not present

Insert IAM MT.

902

Failed to initialize IAM MT

Restart controller or change IAM MT.

903

IAM MT read error

Check that the FW file on the IAM MT root is named exactly MTF6000.FW (manually from PC). Otherwise replace the IAM MT.

904

IAM MT write error

Replace IAM MT.

905

Invalid software on IAM MT

Update software on IAM MT (manually from PC).

906

Flash programming error

Replace the controller.

907

Invalid license on IAM MT

Update software on IAM MT (manually from PC) to a newer version that support the IAM license. Otherwise replace the IAM MT.

908

Incompatible software version

Update software on IAM MT (manually from PC) to a newer version that supports the HW. Otherwise replace the IAM MT.

990

External event

991

External event

992

External event