ATEX Code Definition

The ATEX code is:

Ex II 2 G Ex h IIC T4 Gb

Ex II 2 D Ex h IIIC T110°C Db

  °C ≤ Ta ≤ 40 °C
 

Description

Value

Definition

Equipment group

II

Surface Industry

Equipment category

Group II

2

High level of protection

  • zone 1 (gas)

  • zone 2 (gas)

  • zone 21 (dust)

  • zone 22 (dust)

Atmosphere

 

G

Atmosphere containing Gas, Vapors or Mist

D

Atmosphere containing Dust

Safety design

h

Mechanical product

Gas group

IIC

Hydrogene/ Acetylene

IIB

Ethylene

Dust group

IIIC

Surface combustible dust

Max surface temperature in Gas atmosphere

 

T1 = 450°C

T2 = 300°C

T3 = 200°C

T4 = 135°C

T5 = 100°C

T6 = 85°C

Max surface temperature in Dust atmosphere

 

Example temperatures:

T85°C

T110°C

T120°C

T125°C

T240°C

Special restriction, for example ambient temperature range.

X