Fieldbus Parameters General

Field

Description

Default value

Fieldbus type

Select the fieldbus type from drop-down menu:

  • DeviceNet

  • EtherNet/IP

  • ProfinetIO

  • Profibus

  • CC Link

  • CC Link IE

Undefined

Update interval

Set how often a Process Data Frame should be sent. The value is expressed in milliseconds. Minimum value is 100 ms.

 

Lock tool when fieldbus offline

Selection switch On-Off. Determines the action taken by the controller if the fieldbus module loses communication with the fieldbus master (PLC).

Off

Read result handshake

Selection switch On-Off. When turned On, the setting will affect all virtual stations. The signal Read Result Handshake has to be mapped in the fieldbus configuration.

Any results produced when there are no results to acknowledge will immediately be sent to the PLC.

Results to acknowledge will be put in a queue and when acknowledged it will be cleared and the next result in the queue is sent. The time between the cleared result and the next result in the queue is dependent on the cycle time for the fieldbus set in the general fieldbus settings. If the setting is changed, or if the fieldbus mapping for the virtual station is changed, the results still in the queue will be flushed and not sent to the PLC.

Off

Set by network

Selection switch On-Off. Determines how the fieldbus module communication is configured.

  • On: Communication parameters set automatically in the fieldbus module. Parameters are determined by the network during the initial connection with the far end station.

  • Off: Communication parameters must be entered during the configuration.

Off

Sync on task selected

Off

Byte order Cyclic Data

Select which order of bytes is used for the cyclic data:

  • Set by network

  • Intel (little)

  • Motorola (big)

Set by network

Byte order Acyclic Data

Select which order of bytes is used for the acyclic data:

  • Intel (little)

  • Motorola (big)

Motorola (big)

Load async data automatically

Selection switch On-Off. When turned On, the first and only package of the async data is automatically loaded.

When enable this function, the fieldbus master must ensure that it is done reading data before starting a new cycle.

Off