Internal I/O module

Power supply:

24VDC (18-30VDC)

Inputs/outputs:

8 digital inputs and outputs (24VDC)

Expandable by adding:

up to 7 extension modules each with 8 inputs and outputs

Current per output:

0,5A (max. 3A total)

Fuse protection:

3,5A

Current consumption per input:

7mA

  • Outputs are protected against short circuits, overload, load discharge (inductive voltage spikes) as well as the loss of ground connection.

  • Reversing the polarity of the supply voltage will destroy the soldered fuse.

  • Optionally, the ground potentials of the 24VDC inputs can be separated from those of the 24VDC outputs. The maximum permissible potential difference between the grounds is 100VDC.